Series 1910 in Flame-Proof Enclosure
ATEX/IECEx Approved 1910 Differential Pressure Switch combines advanced design and precision construction to make these switches able to perform many of the tasks of larger, costlier units.
 
Features
	- 
	Flame-proof ATEX enclosure protects the device in hazardous areas 
- 
	Compact size and repeatability, provides a high-value switch for many industrial and OEM applications 
- 
	Wide range of models from 0.07 in w.c. to 20 in w.c. can meet exacting OEM specifications for a low pressure switch 
- 
	Range screw protected inside switch enclosure prevents tampering 
Product Applications
	- 
	Hazardous area low pressure applications 
- 
	Air conditioning refrigeration coil icing detection; defrost cycle initiation 
- 
	Clogged filter detection 
- 
	Variable air volume controller 
Specifications
	- 
	Service: Air and non-combustible, compatible gases. 
- 
	Wetted Materials: Consult factory. 
- 
	Temperature Limits: -30 to 180°F (-34 to 82.2°C); (Note: Product temperature limits differ from case). 
- 
	Pressure Limits: 45 in w.c. (11.2 kPa) continuous, 10 psig (68.95 kPa) surge. 
- 
	Switch Type: SPDT. 
- 
	Repeatability: ±3% FS. 
- 
	Electrical Rating: 15 A @ 120 to 480 VAC, 60 Hz. Resistive 1/8 HP @ 125 VAC, 1/4 HP @ 250 VAC, 60 Hz. Derate to 10 A for operation at high cycle rates. 
- 
	Mounting Orientation: Diaphragm in vertical position. 
- 
	Set Point Adjustment: Screw type on pressure switch inside the Exd enclosure accessible by hole with plug on housing. Setpoint regulation must be done with instrument de-energized. Follow instructions and safety warning to open cover. 
- 
	Enclosure Rating: IP66. IP65 with option OPV, overpressure relief valve. 
- 
	Housing Material: Aluminum. 
- 
	Finishing: Texture epoxy coat RAL7038. 
- 
	Pressure Connections: 1/8" NPT female brass (SS optional). In presence of acetylene it is necessary to use SS. 
- 
	Electrical Connections: Two 1/2" FNPT. Cable gland not included. 
- 
	Weight: 7.49 lb (3.4 kg). 
- 
	ATEX Certificate: BVI 14ATEX0072. 
- 
	Agency Approvals: ATEX Compliant CE 1370 Ex II 2G Ex d IIC T6 Gb / II 2D Ex tb IIIC T85°C Db, -60°C=Tamb=+60°C IECEx Compliant: Ex d IIC T6 Gb / Ex tb IIIC T85°C Db